Faxed bulk materials inspection results, 55 Broadway, 2001

Machine-extracted title · confidence 46%

Faxed chain detailing friable/non-friable asbestos and bulk material sample results.

NYC-WTC_000306165–000306166
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

FrtX ND. • Jan, 08 2000 10:25PM P4 FROM ;

Deer Real Estate Services, Inc page 2 JLC Project #01-2129 Bulk Building Materials Analysis and Procedure

Introduction Polarized light microscopy with dispersion staining (PLM-OS) is the most efficient method for detecting asbestos in bulk samples. It is this method that the JLC lab uses during bulk building material analyses.

Methodology A chain of custody is kept for each sample to ensure proper handling and delivery to the JLC lab prior to analysis. To avoid any possible contamination, ail sample and slide preparation Is carried out in a ventilated, HEPA-filter hood with continuous airflow Sample analysis is performed using PLM-DS in accordance with the USEPA, "Method for the Determination of Asbestos in Bulk Building Materials," EPA 600 R-S3 116, July 1993, and NYDOH-ELAP certification manual, "Polarized Light Microscope Methods for identifying and Quantitating Asbestos in Bulk Samples," ELAP 190.1, October 1993.

Analytical Procedures All samples are subject to preliminary visual stereomicroscopic examination. Observation of homogeneity, fiber identification, and semi-quantitation of constituents can be made at this point. Samples lacking uniformity of composition and/or distribution of component materials then undergo homogenization. Some non-friable organically bound (NOB) samples such as floor tiles and roofing materials may require additional steps to dislodge problem matrices (i.e. ashing, extractions and TEM).

Identification of suspect fibers is made by PLM analysis of subsampies A microscope equipped with dual polarizing filters enables us to observe specific optical characteristics of each sample. Positive identification of asbestos requires determination of the following optical properties; morphology, color and pleochroism, refractive indices, birefringence, extinction characteristics, and signs of elongation.

Asbestos quantitation is performed by point-counting procedure, a standard technique in petrography for determining the relative areas occupied by separate minerals in rock. An ocular reticle superimposes a point or points over the microscope's field of view. The number of points positioned directly above each kind of particle or fiber is recorded. A total of 400 points must be counted over at least eight different representative subsampiBs to complete analysis.

Polarized Light Microscopy JLC uses an Olympus BUT P Polarizing Microscope complete with polarizer, analyzer, port for wave retardation plate, 360 degree graduated rotating stage, substage condenser, lamp and lamp iris, eyepiece reticle, and 25 point Chalkley Point Array Plane polarized light allows for the determination of refraction indices relative to specific crystallographic orientations Morphology and color can also be observed under plane polarized light. Observation of particles or fibers while oriented between polarizing filters whose privileged vibration directions are perpendicular allows for determination of isotropism/ anistropism, extinction characteristics of anisotropic particles, and calculation of birefringence A retardation plate may be placed in the polarized light path for verification of signs of elongation.

Analytical Results The "Summary of Analytical Results" represents the results of analysis. Positive results mean the sample is asbestos or contains more than one percent asbestos by weight The results are generally sufficient for identification and quantitation of major concentrations of asbestos However, it may be found that additional techniques may be necessary. Please be aware that PLM is not consistenly reliable in detecting asbestos in floor coverings and similar NOB materials. Before the material can be considered or treated as non-asbestos containing, confirmabon must be made by quantitative Transmission Electron IVlicroscopy (TEM).

CITY_21MC1OO_O11963438

NYC-WTC_000306166

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000306166Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →