NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality field report, PS 150M, Mar 2002

Machine-extracted title · confidence 45%

IAQ measurements report for PS 150M prior to re-occupancy, March 2002.

NYC-WTC_000300802–000300805
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 1«, 2002 Indoor Air Quality Assessment Page 3 P. S. ISOM ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at approximately 1:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.1.°F to 75.6°F. Five (5) of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 56.3 to 57.6°F.

RelatiyeJIumiditv

The relative humidity indoors ranged from 37.5 to 50.1 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 56.3 to 59.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 491 ppm to 840 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 428 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1128 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC ’ s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations were 0 ppm for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 45 pg/m^ to 79 pg/m^. Twenty- four (24) of the indoor measurements were above the NPAAQS of 65 pg/m^- All thirty (30) of the indoor measurements were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 70 pg/m^. The PM2.5 average concentration was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor

CITY_21MC100_0 04151960

NYC-WTC_000300804

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000300804Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →