Indoor air quality report, High School for Leadership & (M894),

Machine-extracted title · confidence 31%

ATC IAQ report for Feb 13, 2002 at the referenced school.

NYC-WTC_000297790–000297793
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan February 14,2002 Indoor Air Quality Assessment Page 4 H S for Leadership & Pub Service (M894) ATC Protect No 15-19125-0290

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm) The outdoor TVOC concentration was also 0 0 ppm

OBSERVATIONS

During this assessment, ATC noted the following • The interior of the building appeared clean and free of dust and debris, • The building was occupied at the time of the assessment, • No smoke odor was detected m the building.

FINDINGS

Based on the real-time measurements, the following findings are presented

1. Concentrations of respirable particulates, CO and TVOCs, were within applicable standards and guidelines 2. Six (6) temperature measurements were below the range of 68 to 75°F (at 50 percent relative humidity recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). 3. One hundred and thirty-one (131) of the relative humidity measurements were below the ASHRAF recommended range of 30 to 60 percent for occupant comfort The other three (3) measurements were within the recommended range 4. Three (3) CO2 measurements were above the range recommended by ASHRAF 62-1999 All others were below the recommended maximum concentration

It is our pleasure to provide these indoor air quality services to the New York City Board of Education If you have any questions about this report, please call (212) 353-8280, extension 261 or 212

Smcerely, 1TC ASSOCIA TES INC. Reviewed by.

Yiannis Efstathiou James R Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC1OO_OO3O88O45

NYC-WTC_000297793

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000297793Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297826

ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297808

ATC indoor air measurements report for February 14, 2002 at the school.

Similar indexed content

Compare copies and versions →