March 22, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗March 25, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
NYC-WTC_000295919–000295922OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr Bernard P Orlan March 26 2002 Indoor Air Quality Assessment Page 2 H S for Leadership <S, Public Service (M894) ATC Protect No 15 19125 0290
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities
EVALUATION CRITERIA
Currently there are no regulatory standards for indoor air quality in non industrial buildings such as offices and schools For the real time data collected ATC uses the commonly accepted guidelines cited in the following publications
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62 1999) Amencan Society of Heating Refrigerating and Air Conditioning Engmeers (ASHRAE), Thermal Environmental Conditions for Human Occupancy (ASHRAE 55 1992) Industrial Hygienists Guide to Indoor Air Quality Investigations (1993) American Industrial Hygiene Association (AIHA)
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation Meeting one some or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
% Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2 5) of air (pg/m3) 24 hour average 40 pg/m^ 24 hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer 73 79°F at 50% RH ASHRAE 55 Winter 68 75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient Air Quality Standard AHA = Amencan Industrial Hygiene Association
CITY_21MC100_003085589
NYC-WTC_000295920
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000295915
March 22, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295866
ATC report on indoor air quality measurements at NYC school; March 14, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295749
ATC memo describing IAQ measurements at the referenced NYC school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295745
ATC memo about IAQ measurements at a NYC school for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295792
ATC report on IAQ measurements conducted at the referenced NYC school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295726
ATC Associates memo documenting indoor air quality measurements at a NYC school.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350853
DOE-DOE indoor air quality assessment report for PS 126M 80.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295768
ATC report of IAQ measurements at a NYC school for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350868
Report of IAQ measurements prior to school resumption.
9 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350857
DOE air quality report and scope of work for PS 126M.
9 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297826
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297874
ATC report of IAQ measurements collected on Feb 28, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000295928
March 27, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297757
ATC quality report for IAQ measurements at a NYC high school in Feb 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295923
March 26, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297704
Indoor air quality report for Feb 11, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295895
March 2002 IAQ measurements at a NYCBOE school to assess air quality maintenance.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295890
March 2002 IAQ measurements at selected NYCBOE school for QA purposes.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000295915
March 22, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
Similar indexed content
NYC-WTC_000295866
ATC report on indoor air quality measurements at NYC school; March 14, 2002.
Similar indexed content
NYC-WTC_000295749
ATC memo describing IAQ measurements at the referenced NYC school.
Similar indexed content
NYC-WTC_000295745
ATC memo about IAQ measurements at a NYC school for BOE.
Similar indexed content
NYC-WTC_000295792
ATC report on IAQ measurements conducted at the referenced NYC school.
Similar indexed content