NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

IAQ field report letter, Oct 17, 2001

Machine-extracted title · confidence 41%

IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.

NYC-WTC_000292901–000292905
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan October 17, 2001 Indoor Air Quality Assessment Page 3 Stuyvesant High School (Md??) ATC Project No. 15-19125-0246

SAMPLING RESULTS

Real-Time Environmental Measurements

ATC collected one hundred and fourteen (114) sets of real-time environmental measurements consisting of one hundred and twelve (112) in the school building and two (2) outdoors. These results are described below. Field data sheets are found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged from 68,2 °F to 75.9 °F. Eight (8) measurements were below the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These readings were on the 3’"*^, 4th, gth and lO^h floors. The outdoor temperature range was 68.2to75.9°F.

Relative Humidity

The relative humidity indoors ranged from 44.4 percent to 57.5 percent. All measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 50.4 to 60.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 394 ppm to 2015 ppm. Thirteen (13) CO2 measurements were at or above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 374 ppm. Therefore, the acceptable level of CO2 at this location was 1074 ppm (background level + 700 ppm). Rooms with high CO2 levels were found on the 3’’^, 4ih 6th and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 - 1 ppm.

Respirable Particulates

Respirable particulate concentrations indoors ranged between 12 pg/m^ and 37 pg/m^. All concentrations were below the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration range was 25 to 35 pg/m^.

CITY_21MC100_003081597

NYC-WTC_000292903

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000292903Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271233

Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.

Similar indexed content

Compare copies and versions →