Mr. Bernard P. Orlan May 29, 2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Sendee (MS94 i ATC Project No. 15-19125-0290
Real-Time environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
.Attachment. Readings were collected in the morning and evening. The results are described
below.
Temperature
Indoor dry bulb temperature measurements ranged from 74.4°F to 81.9°F. Five (5) of the indoor
measurements for temperature were above and no measurements were below the range of 73 to
79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the
summer season. The outdoor temperature ranged from 77.5 to 80.4°F.
Relative Humidity
The relative humidity indoors ranged from 51.0 percent to 58.6 percent. All of the indoor
measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity range was 55.1 to 59.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 501 ppm to 1121 ppm. All of the indoor
measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 689 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1389 ppm (background level 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor
air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. 'The outdoor CO concentrations ranged
from 1 ppm to 3 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 24 pg/m^ with an
average 11 pg/m^' None of the indoor measurements for PM2.5 were above the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m3 for sensitive
individuals such as asthmatic people and children. The outdoor respirable particulate
concentrations ranged from 53 pg/m^ to 82 pg/m^ with an average of 67 pg/m^.