Mr. Bernard P. Orlan May 28, 2002
Indoor Air Quality Assessment Page 4
H.S. for Leadership & Public Service fM894) ATC Project No. 15-19125-0290
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the
AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines.
2. Two (2) of the indoor measurements for temperature were below and no readings were above
the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE
Standard 55-1992 during the summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals
such as asthmatic people and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or
212.
Sincerely,
J TC ASSOCIA TES INC.
Reviewed by:
^el Java/ I James R. Cohn, CIH, CSP
Senior Projeyt Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC1OO_OO3O79557
NYC-WTC_000291945