NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, Leadership & [name], May 2002

Machine-extracted title · confidence 42%

Report of indoor air quality measurements at 90 Trinity Place, May 2002.

NYC-WTC_000291910–000291913
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 23, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service fM894) ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. ryPC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared dead and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Sixty-eight (68) of the indoor measurements for temperature were below and sixty (60) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. One hundred and eight (108) of the indoor measurements for relative humidity were below and twenty (20) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1326 ppm) was taken in room 306 at 1:53 PM with 30 occupants. 5. None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or 212.

Sincerely, A TC ASSOCL4 TES INC. Reviewed by:

James R. Cohn, CIH, CSP iject Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_003079519

NYC-WTC_000291913

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000291913Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000399272

May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.

Similar indexed content

Compare copies and versions →