Indoor air quality report, HS Leadership & [name], May 2002

Machine-extracted title · confidence 42%

Indoor air quality measurements report for 90 Trinity Place, May 2002.

NYC-WTC_000291841–000291845
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 17, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

nNDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines. 2. One (1) of the indoor measurements for temperature was below and two (2) were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE- recoramendcd range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthrhatic people and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or 212.

Sincerely, A rC ASSOCIATES INC. Reviewed by­

James R. Cohn, CIH, CSP Senior Preset Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_003079443

NYC-WTC_000291844

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000291844Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000211863

Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 27, 2002, to evaluate possible contamination.

Similar indexed content

Compare copies and versions →