Mr. Bernard P. Orlan May 17, 2002
Indoor Air Quality Assessment Page 4
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the
AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following;
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
nNDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines.
2. One (1) of the indoor measurements for temperature was below and two (2) were above the
range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard
55-1992 during the summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recoramendcd range of 30 to 60 percent for occupant comfort.
4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as
asthrhatic people and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or
212.
Sincerely,
A rC ASSOCIATES INC.
Reviewed by
James R. Cohn, CIH, CSP
Senior Preset Manager Regional Manager
Industrial Hygiene Division