Mr. Bernard P. Orlan March 4, 2002 Indoor An Quality Assessment Page 4 P. S. 150M ATCProiect No. 15-19125-0289

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

rypC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • There was construction work going on in the plaza; • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. None of the PM2.5 measurements were above the NPAAQS of 65 pg/m^ or above the USEPA recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and children. 3, Fourteen (14) of the temperature measurements were above the range of 68 to 75O F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season ( wintertime conditions). 4. .All indoor measurements of relative humidity were below the ASHRAJc recommended range of 30 to 60 percent for occupant comfort. 5. All COa measurements were below the range recommended by ASHRyAE 62-1999.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

Sincerely, Reviewed by: 4 re ASSOCL4 TES INC.

Amel Jav^t James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CIT Y_2 IMCIO 0_0 0 2 95 43 5 4'

NYC-WTC_000289493

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000289493Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS 150M, Mar 2002

NYC-WTC_000289398

Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.

Similar indexed content

NYC-WTC_000375489

Indoor air quality measurements collected Feb 28, 2002 for PS 150M.

Similar indexed content

Compare copies and versions →