Ml-. Bernard P. Orlan March IS, 2002
Indoor Air Quality Assessment Page 4
P S. 150M_____________________________________________ ATC Project No. 15-19125-0289
respirable particulate concentration measurements ranged from 100 to IIS pg/m^ with an
average of 112 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TJ'OC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was construction work going on in the plaza;
• Tire school building was occupied at the time of the assessment;
• No smoke odor was detected m the building;
BINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, CO2 and TVOCs were within applicable standards and guidelines;
2. Twenty-four (24) of the indoor PM?.5 measurements were above the NPAAQS of 65 pg/m^.
All thirty (30) of the indoor measurements were above the USEPA recommended PM2.5
concentration of 40 pg/m-^ for sensitive individuals and children. All of the outdoor PM2.5
measurements were above the NPAAQS of 65 pg/m^ and the USEPA recommended PM2.5
concentration of 40 pg/m^ for sensitive individuals and children.
3. Five (5) of the temperature measurements were above the range of 68 to 75® F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions).
4. All measurements of relative humidity were within the ASHRAE recommended range of 30
to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely, Reviewed by:
/I TC ASSOCIA TES INC.
Yiannts Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_0 02954264