IAQ measurements collected at PS 150 M for re-occupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗ATC IAQ field report for P.S. 150M dated March 26-27, 2002.
NYC-WTC_000289402–000289405OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 27, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATCPr^t No. 15-19125-0289
rhe assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
PZVALUATIONCRITE^RIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications;
VenUlation for Acceptable Indoor Air Quality (ASHJ14E 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992): Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET (.UIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
gags Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon M onoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m-^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary .Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002954199
NYC-WTC_000289403
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000289426
IAQ measurements collected at PS 150 M for re-occupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214358
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 8, 2002, for pre-reoccupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289478
ATC memo detailing IAQ measurements conducted at PS 150M for BOE re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375489
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289370
ATC indoor air quality measurements at PS 150 M for BOE prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392600
ATC report detailing IAQ measurements conducted April 9, 2002 at P.S. 89M per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300633
ATC IAQ report covering measurements at PS 150M for re-occupancy
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374708
ATC IAQ measurements at P.S. 150M for BOE air quality assessment, April 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400606
Indoor air quality measurements collected for BOE at PS 89M.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249692
Indoor air quality measurements at PS 150M prior to re-occupancy.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410613
Letter report presenting indoor air quality measurements at PS 150M, Feb 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374832
IAQ measurements at PS 150M for re-occupancy evaluation, May 23, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300705
ATC IAQ measurements at PS 150M before occupancy, Feb 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000289426
IAQ measurements collected at PS 150 M for re-occupancy evaluation.
Similar indexed content
NYC-WTC_000214358
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 8, 2002, for pre-reoccupancy evaluation.
Similar indexed content
NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similar indexed content
NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
Similar indexed content
NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
Similar indexed content