A2.8 Lead Surface Dust

All dust wipe samples taken were analyzed in accordance with EPA7082 method via Flame Atomic Absorption (FAA).

Dust wipe results were considered satisfactory when the levels obtained were below the ERA new levels for clearing a work area for re-occupancy after an ERA defined lead abatement is performed, as specified in 40 CFR §745.227(e) (8) (viii). Floors 40 micrograms of lead per square foot Window Sills 250 micrograms of lead per square foot

Dust wipe results shall be considered unsatisfactory when the levels obtained are greater than the EPA new levels for clearing a work area for re-occupancy after an EPA defined lead abatement is performed, as specified in 40 CFR §45.227(e) (8) (viii). Floors 40 micrograms of lead per square foot Window Sills 250 micrograms of lead per square foot

Results from samples collected were reported to BOE, UFT, School Principal and the PA consultant within 24 hours.

In the event that unsatisfactory results are obtained, the following actions were to be implemented:

1. Perform general dust clean up of all areas/classrooms with unsatisfactory results.

2. Lead specific cleaner shall be utilized.

3. Re-test said areas following clean up. 4. Floor mats and/or other dust control devises shall be placed at points of entry. /

Actions 1,2 and 3 shall be repeated until satisfactory results are obtained.

A2.9 Silica

First floor lobby - one sample during the school day.

All samples collected were analyzed utilizing the NIOSH 7500 method for respirable silica.

Since, there are no regulatory standards for Mineral Dust in non-industrial buildings, such as offices and schools at this time, the OSHA standard 1910.1000 TABLE Z-3 were utilized (in accordance with the protocol request of PA consultant).

A;\e_RatroflttlngHV AC_R.Cascono.doc

Page A2-4

CITY_21MC100_010274220

NYC-WTC_000278833

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278833Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →