Note: Mechanical Engineer hired by the BOE, Robert Cascone, P.E. of Burns & Roe explains that HEPA filters are intended for use in a "Clean Room", such as a hospital operating room. The air handling systems at the school cannot use HEPA filters (rated for 0.3 microns at 99.9% efficiency), but the proposed filter retrofitting is a practical way to vastly improve filtration in the HVAC system. In the central systems, filtration is increased from 40% at 1 micron to 90-93%, and in the univents from 40% at 1 micron to 87%. The Odor Guard III has a high charcoal content to remove odors and VOCs.

Week of 12/17/01

12/19 Meeting with Facilities Committee and the BOE.

BOE agreed to hire a permanent custodian to maintain ventilation system and filter replacements.

12/19 Samples taken of floor tiles and ceiling tiles were found to be free of asbestos.

Tom Fusillo notes the current method used to test for microscopic dust particles may yield false high readings. He recommends an alternative device be used. The testing/monitoring firm ATC Associates inc. representative, Andreas Andreou has ordered the new device.

Psychological group met with District 2 representatives. Discussion about implementing and improving and psychological plans for parents, teachers, and children.

All ducts have been vacuumed and cleaned. Central HVAC system cleaned - wiped and vacuumed

Week of 12/24/01

As a test, four types of HVAC filters are installed in 4 classrooms in the incremental units. (Protocol was decided at a meeting with representatives of PTA, LIFT, NYC-BOE, ENVIRON, ATC Associates, Inc., Bums & Roe, and Environmental Dynamics Corp.) Two types of odor-guard filters with activated charcoal, an electrostatic filter, and the original blue filters are tested. An air quality particulates test will compare them against each other (and against the original univent filter). Testing is to be performed for 1 week from December 29 through January 5. ATC Associates, Inc. set up PM2.5 sampling devices (Dust-Trak*) to continuously monitoring these four classrooms for one week. (Test results showed low particulate counts by all filters, and no significant difference among them.)

Cleaning of play “yard” completed. (Includes removal and cleaning of rubber mats, cleaning under mats, cleaning surfaces, and removal and replacement of a layer of soil)

Week of 12/31/01

Environmental cleaning is scheduled for interior spaces (such as classrooms, library, etc.), including contents. To be performed by School Construction Authority contractors.

1/3 Meeting of psychological group with teachers, administrators, and St Vincent's to brainstorm, develop, and improve a set of psychological plans for parents, teachers, children, and administrators. St. Vincent’s responsible for producing compiled plan.

Week of 1/07/02

Preliminary air quality and wipe test results of 12/19 and 12/20 were sent to Environ for review.

The filters will be run, and the spaces will be tested for contaminants in the air.

lEnvironmental Cleanup and Preparation of PS/IS 89 -PAGE 4- 1/15/02|

CITY_21MC100_012173164

NYC-WTC_000276319

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000276319Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000106411 · Box DEP Box 37

Union memorandum regarding environmental monitoring and cleanup protocols following the closure of Stuyvesant High School after the September 11 attacks.

Similar indexed content

NYC-WTC_000149798 · Box DEP Box 10

Generic form or header page from the Department of Environmental Protection regarding general World Trade Center notices and requests.

Similar indexed content

Compare copies and versions →