Mr. Bernard P. Orlan February 11, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environments.! measurements consisting of eight (8)
outdoors and thirty-two (32) inside in the morning (A.M.) and the same number of readings in
the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are
found in the .Attachment. Readings began at 8:50 A.M. and concluded after 4:00 P.M. The
results are described below:
Temperature
Indoor dry bulb temperature measurements ranged from 67.5°F to 73.6°F (A.M.) and 68.6°F to
73.4°F (PM). In the morning, only one (1) measuremenc, in the unoccupied Dance Room, was
below the range of 68 to 75°F (at 50 percent relative humidity) recommended by A,SHRAE
Standard 55-1992 during the heating season (wintertime conditions), none were above. In the
afternoon, all measurements were within the recommended range. The average outdoor
temperature was 53.7°F (A.M.) and 55.6°F (P.M.).
Relative Humidity
The relative humidity indoors ranged from 18.9 to 26.7 percent (A.M.) and 18.5 to 22.6 percent
(P.M.). All measurements below the ASHRAE-recomrnended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity averaged 25.9 percent (A.M.) and 18.3 percent
(P.M.).
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 518 to 999 ppm (A.M.) and 481 to 990 ppm
(P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The outdoor
(background) CO2 concentrations averaged 480 ppm (A.M.) and 449 ppm (P.M.). Therefore, the
maximum acceptable level of CO2 at this location was 1180 ppm (background level + 700 ppm).
The highest indoor level was measured in Classroom 402. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 2’^*^
and 3^^ floors of the school building were not occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide was not detected indoors (0 ppm). The outdoor CO concentration was 0 ppm
(A.M.) and 1 ppm (P.M.).
Respirable Particulates ('PM2j)
Respirable particulate concentrations* indoors ranged from 17 pg/m^ to 37 pg/m^ (A.M.) and
10 pg/m^ to 22 pg/m^ (P.M.). All indoor measurements were below the NPAAQS of 65 pg/m^
(24-hour average). The average PM2.5 concentration* for the entire school building was
approximately 27 pg/m^ (A.M.) and 18 pg/m^ (P.M.). T^one of the indoor measurements were
above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as