NYC-WTC_000274071–000274074OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan .lune 4, 2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATIOINCRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Healing, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA),
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMETER TARGETLEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambienl-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC1OO_OO31O7161 NYC-WTC_000274072
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000401956
ATC indoor air quality measurements report for Stuyvesant High School dated Feb 11, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311574
ATC IAQ measurements report for Stuyvesant High School, Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401989
ATC IAQ report for Stuyvesant High School dated Feb 13, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311608
ATC IAQ measurements report for Stuyvesant High School dated February 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311536
ATC IAQ measurements report for Stuyvesant High School, Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372924
ATC delivers IAQ report for Stuyvesant High School (M477) dated May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311502
ATC IAQ measurements report for Stuyvesant High School, Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311627
Correspondence and IAQ measurements report for Stuyvesant High School dated February 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401971
ATC indoor air quality measurements report for Stuyvesant High School dated Feb 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406911
Report of IAQ measurements at Stuyvesant High School prepared for Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000311402
ATC memo detailing IAQ measurements at Stuyvesant High School for Feb 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406827
May 22, 2002 IAQ report for Stuyvesant High School, Board of Education project 15-19125-0246.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336187
Report of indoor air quality measurements collected April 15, 2002 at Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336073
May 2002 indoor air quality measurements at Stuyvesant High School, per BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229470
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407047
Report of IAQ measurements collected June 24, 2002 at Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000401956
ATC indoor air quality measurements report for Stuyvesant High School dated Feb 11, 2002.
Similar indexed content
ATC IAQ measurements report for Stuyvesant High School, Feb 2002.
Similar indexed content
NYC-WTC_000401989
ATC IAQ report for Stuyvesant High School dated Feb 13, 2002.
Similar indexed content
ATC IAQ measurements report for Stuyvesant High School dated February 14, 2002.
Similar indexed content
ATC IAQ measurements report for Stuyvesant High School, Feb 2002.
Similar indexed content