NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
NYC-WTC_000271218–000271222OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan October 30, 2001 Indoor Air Quality Assessment Page 2 Stuvvesant High School (M477) ATC Project No. 15-19125-0246
Tlie assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in air contaminant concentrations, and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the Board of Education as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
CuiTcntly, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-]999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-]992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
yPARAhteTER.;)- lAKGEILEVEL • )'0tGi^^TldNr:‘" •'A
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ASHRAE 62) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Temperature Summer: 73-79°F at 50% RH ASHRAE55 Winter: 69-76°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile 1 ppm Organic Compounds AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Aii' Quality Standard ■AIHA = American Industrial Hygiene Association
CITY_21MC100_003100297
NYC-WTC_000271219
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292918
IAQ field report for Stuyvesant H.S. dated Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292901
IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000188540
Report detailing an indoor air quality assessment conducted at a school on Chambers Street on October 25, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292967
Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312060
ATC IAQ assessment conducted at Stuyvesant High School on November 14, 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
Similar indexed content
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
Similar indexed content
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similar indexed content
NYC-WTC_000292918
IAQ field report for Stuyvesant H.S. dated Oct 18, 2001.
Similar indexed content
NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
Similar indexed content