NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

IAQ assessment report, Stuyvesant HS, Oct 2001

Machine-extracted title · confidence 28%

ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.

NYC-WTC_000271213–000271217
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan October 26, 2001 Indoor Air Quality Assessment Page 4 Stuyvesant High School ('M477) ATC Project No. 15-19125-0246

TVOC Concentration

TVOC concentrations indoors were 0.0 ppm for all readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • . The building was occupied at the time of the assessment; • All windows were closed except for windows in Room 931 and Room 1004; • No smoke odor was. detected in the building;

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Twelve CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Five (5) temperature measurements were above the range recommended by ASHRAE 62- 1999. -

4. One (1) relative humidity measurement was marginally above the range recommended by ASHRAE 55-1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in sorne rooms to be uncomfortable. The elevated CO2 levels indicate the need for increased outdoor air. ■ <

CITY_21MC100_003100267

NYC-WTC_000271216

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000271216Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000293059

Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.

Similar indexed content

NYC-WTC_000293095

Indoor air quality assessment report for Stuyvesant High School conducted for NYC Department of Education.

Similar indexed content

Compare copies and versions →