NYC 9/11 Public Portal Document
Attn: Mr. Bernard Orlan Received; 2/18/02 4:00:00 PM
N.Y.C. Board of Education ATC Group#: 6732
28-11 Queens Plaza North Analysis Date: 2/22/02
Long Island City, NY 11101
Fax; (212)475-4122 Phone: (212)477-8941
Project: NYC-BOE PS 234M Project#: 14584-1823
292 Greenwich St., New York, NY
Asbestos Fiber Analysis by Transmission Electron Microscopy (TEM) Performed
by EPA 40 CFR Part 763 Final Rule (AHERA)
Analytical Asbestos
Area l^on Asbestos # Structures Sensitivity Concentration
Sample rolume Analyzed Asb Type(s) 0.5p-5 5p (S/cc) (S/mm‘) (S/cc) Notes
09 1920.00 0.0450 0 None Detected 0 0 0.0045 <22.24 <0.0045
6732 -9
10 1920.00 0.0450 0 None Detected 0 0 0.0045 <22.24 <0.0045
6732 -10
1! 1920.00 0.0450 0 None Detected 0 0 0.0045 <22.24 <0.0045
6732 -11
'2 2000.00 0.0450 0 None Detected 0 0 0.0043 <22.24 <0.0043
6732 -12
13 2016.00 0.0450 0 None Detected 0 0 0.0042 <22.24 <0.0042
6732 -13
14 2016.00 0.0450 0 None Detected 0 0 0.0042 <22.24 <0.0042
6732 -14
'5 2016.00 0.0450 0 None Detected 0 0 0.0042 <22.24 <0.0042
6732 -15
ROMAN PEYSAKHOV MICHAEL A. GORYCKl, Ph.D.
Analyzed by: Approved by;
I Disclaimer: The laboratory is not responsible for data reported in structures/cc, which is dependent on volume collected by non-laboratory personnel. This lab is only responsible |
i for data repotted in structures/mm’. This report may not be reproduced, except in toll, without written approval by ATC Associates Inc. This report may not be used to claim '
i product endorsement by NVLAP or any other agency of the U.S. Government. This reports relates only to the samples reported above. Quality control data (including 95%
i confidence limits and laboratory and analysis' accuracy and precision) is available upon request
Accredited for NVLAP PLIWTEM #101187-0, NY State ELAP #10879
CONFIDENTIAL, CITy_21MC100_003468015
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000263013
OCR can misread numbers and units. Confirm readings against the page image before using them.