Mr. Bernard P. Orlan May 17,2002 Indoor Air Quality .Assessment Page 3 H.S. for Leadership & Public Service fM894) ATC Project No. 15-19125-0290
Real-Time environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 72 °F to 81.6 °F. One (1) of the indoor measurements for temperature was below and two (2) were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 77 to 84.6 °F.
Rele/tive Humidity
The relative humidity indoors ranged from 30.2 percent to 42.3 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 19.6 to 32.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 421 ppm to 1236 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <:700 ppm above the background level. The outdoor (background) CO2 concentration was 566 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1266 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary' source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. I'hese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 ug/m3 to 25 pg/m3 with an average 13 pg/m^- All the indoor measurements for PM2,5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 47 pg/nU to 56 pg/m^ with an average of 52 pg/'m^.
CONFIDENTIAL, CITY_21MC100_003464318 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260385
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000260517
ATC IAQ measurements collected May 31, 2002 at High School for Leadership & [name].
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260521
ATC IAQ measurements collected June 3, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260112
ATC IAQ measurements collected April 18, 2002, at the referenced school per BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260509
ATC report of indoor air quality measurements collected at the referenced school in May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260505
ATC IAQ measurement report for High School for Leadership & [name], May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397419
ATC IAQ report for P.S. 234M with May 2002 sampling details.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410935
ISO/IEC quality systems-related material associated with project records.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260529
ATC IAQ measurements collected June 5, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335281
Indoor air quality measurements at M894; June 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335402
ATC IAQ measurements collected February 12, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260329
ATC IAQ measurements at the referenced school, BOE request noted.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260401
ATC IAQ measurements collected May 17, 2002 for BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260505
ATC IAQ measurement report for High School for Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291841
Indoor air quality measurements report for 90 Trinity Place, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260401
ATC IAQ measurements collected May 17, 2002 for BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291805
Report of lAQ measurements for HS Leadership at 90 Trinity Place, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399478
BOE-ordered IAQ measurements at 90 Trinity Place for High School for Leadership, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399348
IAQ measurements collected May 14, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000260517
ATC IAQ measurements collected May 31, 2002 at High School for Leadership & [name].
Similar indexed content
NYC-WTC_000260521
ATC IAQ measurements collected June 3, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000260112
ATC IAQ measurements collected April 18, 2002, at the referenced school per BOE program.
Similar indexed content
NYC-WTC_000260509
ATC report of indoor air quality measurements collected at the referenced school in May 2002.
Similar indexed content
NYC-WTC_000260505
ATC IAQ measurement report for High School for Leadership & [name], May 2002.
Similar indexed content