ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗April 2002 IAQ measurement summary for the referenced high school.
NYC-WTC_000260159–000260162OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 26, 2002 Indoor Air Quality Assessment Page 2 H.S. for Leadership & Public Service (M894)_______________ ATC Project No. 15-19125-0290 The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, P.efrigerating, and Air-Conditioning Engineers (ASHRAE); Iliermal Environmental Conditions for Human Occupancy (ASHRAE 52-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL "F/S: AGENCY OR ORGANIZATION Carbon Dioxxie <700 parts per million (ppm) ASIIEAf 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79“F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_003464061 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260160
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000260120
ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259995
IAQ measurements collected Mar 14, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296812
ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394809
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260116
ATC IAQ measurements collected April 19, 2002 for HS Leadership; BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000254302
Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370501
Indoor air quality measurements collected March 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260227
May 2, 2002 IAQ measurements requested by BOE for school.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000409958
ATC report of IAQ measurements at High School for Leadership, March 2002, for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000291755
Indoor air quality measurements report for the school at 90 Trinity Place, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410923
Indoor air quality measurements and BOE coordination for H.S. for Leadership, June 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260209
May 2002 IAQ measurements requested by BOE for the school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260263
May 6, 2002 IAQ measurements for the school; BOE involvement.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000260120
ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
Similar indexed content
IAQ measurements collected Mar 14, 2002 for BOE
Similar indexed content
NYC-WTC_000296812
ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
NYC-WTC_000260116
ATC IAQ measurements collected April 19, 2002 for HS Leadership; BOE program.
Similar indexed content