Mr. Bernard P. Orlan April 16, 2002 Indoor Air Quality' Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Proiect No. 15-19125-0290 RlA^L-Tjyi [Ml NVIRONMENTAL MEASUREMENTS
ATC collected one hundred and thirty-seven (137) sets of real-time environmental measurements consisting of one hundred and twenty-six (126) in the school building and eleven (11) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 7.15 A.M. and concluded after 2:55 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 59.2 °F to 80 °F. Two (2) indoor measurements for temperature were below, one hundred nineteen (119) measurements were above, and five (5) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 67.7 °F to 79.5 °F.
Relative Humidity
The relative humidity indoors ranged from 33.5 percent to 62.9 percent. Eight (8) of the indoor measurements for relative humidity were above, one hundred and eighteen (118) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 42.1 to 64.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 132 ppm to 1529 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 742 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1442 ppm (background level + 700 ppm). The highest reading was measured in the basement hallway at 2:55 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of (302 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 3 ppm. These concentrations were below the NP'AAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations are 2 ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 21 pg/m^ with an average 14 pg/m^- All of the indoor and outdoor measurements for PM2 5 were below the NP.AAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodvriam c diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 11 pg/m^ to 51 pg/m^ with an average of 13 pg/m3. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITy_21MC100_0 03463929 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260102
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370492
Indoor air quality measurements collected March 12, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180188
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259977
IAQ measurements collected Mar 13, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260177
April 29, 2002; cover about IAQ measurements at the school.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179972
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
Similar indexed content
Indoor air quality measurements collected March 12, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
Similar indexed content
NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
Similar indexed content
Indoor air quality measurements collected March 21, 2002 at the referenced school.
Similar indexed content