Indoor air quality report, High School of Economics and Finance,

Machine-extracted title · confidence 42%

IAQ measurements conducted April 15, 2002 at the referenced school for BOE evaluation.

NYC-WTC_000259188–000259191
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 16, 2002 Indoor Air Quality’ Assessment Page 2 H.S. of Economics and Finance fM8331 ATC ProiectNo. 15-19125-0291

The results of the sampling represent conditions found on the dates of the siiivey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVAl.UATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such rs offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASH1L4E 62-1999), American Society o:' Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), Americar. Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE I TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

PAJRAMETER iTARGETtLEVEIj': AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO;;) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO)_____________ USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m3) 24-hour average 40 pg/m ’ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Rela ive Huir idity 30 - 60 % ASHRAE 55 Tota Volatile Organic Compounds 1 ppm AIHA (TVOC) USEP/\ = United States Environmental Protection Agency NPAAJS == National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

CONFIDENTIAL, CITY_21MC100_003462252 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259189

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259189Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →