IAQ report, High School of Economics and Finance, Mar 2002

Machine-extracted title · confidence 32%

Indoor air quality measurements collected March 26, 2002 for school.

NYC-WTC_000259153–000259156
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 27, 2002 Indoor Air Quality Assessment Page 2 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 The i csults of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air qualiy control activities.

EVALUATION CRITERIA

Curre ntly, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air qualit)' will be achieved at all times.

TABLE 1 TARtSET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Cart on Dioxide <700 parts per million (ppm) ASHRAE 62 (CO?)____________ above background level Cart on Monoxide 9 ppm ASHRAE 62 (adopted from (CO I_____________ USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^ ) 24-hour average 40 pg/m3 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS == National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

CONFIDENTIAL, CITY_21MC100_003462153 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259154

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259154Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259157

ATC notes and observations for IAQ measurements at the school, March 2002.

Similar indexed content

NYC-WTC_000259180

IAQ measurements collected April 11, 2002 for BOE program.

Similar indexed content

Compare copies and versions →