IAQ report, High School of Economics and Finance, Mar 2002

Machine-extracted title · confidence 33%

Indoor air quality measurements submitted to BOE for the High School of Economics and Finance, March 2002.

NYC-WTC_000259111–000259115
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 18, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance fM833) ATCProiectNo. 15-19125-0291 24-hciur average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concenlration

TVO(?s indoor concentrations ranged from 0 to 0.5. The concentrations were below the AIHA recommended guideline of 1 ppm. The outdoor TVOC outside concentration was 0.0 ppm for all readings.

OBSPZRVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Eight (8) of the indoor measurements for temperature were above and seventy-seven (77) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Eighty-four (84) of the indoor measurements for relative humidity were within and four (4) were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1380 ppm) was measured in the basement hallway by the gymnasium area at approximately 10:15 AM with 20 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of ai'ailable outdoor air. The primary source of CO2 indoors is occupant respiration. 5. Three (3) of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Six (6) of the eighty-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

CONFIDENTIAL, CITY_21MC100_003462047 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259114

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259114Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000384207

Indoor air quality measurements at HS of Economics & Finance for BOE, March 2002.

Similar indexed content

NYC-WTC_000402495

Indoor air quality measurements collected on March 15, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000219378

ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.

Similar indexed content

NYC-WTC_000402524

Indoor air quality measurements collected March 19, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →