Mr. Bernard P. Orlan February 26, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty-four (124) sets of real-time environmental measurements consisting of one hundred and twenty-two (122) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 1:05 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.4°F to 73.7°F. All of the . measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 45.7 to 51.8 °F.
Relative Humidity
The relative humidity indoors ranged from 26.1 percent to 32.6 percent. Forty-one (41) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The rest of the measurements were below the recommended range. The outdoor relative humidity levels were 30.1 and 32.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 526 ppm to 1196 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 533 and 568 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1268 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk.. Carbon dioxide measurements are used .as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. .'4
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 to 1 ppm.
Respirable Particulates (PM2_5) ■ ‘ ?
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 22 pg/m^ with an average of approximately 16 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 32 and 35 pg/m^.
CONFIDENTIAL, CITY_21MC100_003457989 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000256148
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000256164
Indoor air quality measurements conducted at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256198
IAQ measurements collected for Stuyvesant High School in Feb–Mar 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256181
Report of IAQ measurements at Stuyvesant High School per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256216
IAQ measurements collected for Stuyvesant High School in Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256233
IAQ measurements collected for Stuyvesant High School (Mar 2002).
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336329
ATC IAQ measurements collected on Mar 1, 2002 for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255959
February 6, 2002 IAQ measurements for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256046
ATC memo for Stuyvesant High School IAQ measurements dated February 13, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255705
Report of IAQ measurements at Stuyvesant High School, Jan 25, 2002, for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336411
ATC IAQ report for Stuyvesant HS; measurements collected March 11, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256013
ATC memo accompanying IAQ report for Stuyvesant High School, February 12, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256238
IAQ measurements collected for Stuyvesant High School (Mar 2002).
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000256198
IAQ measurements collected for Stuyvesant High School in Feb–Mar 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256164
Indoor air quality measurements conducted at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000269995
March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256181
Report of IAQ measurements at Stuyvesant High School per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336411
ATC IAQ report for Stuyvesant HS; measurements collected March 11, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402099
ATC IAQ measurements conducted on Feb 28, 2002 for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements conducted at Stuyvesant High School.
Similar indexed content
NYC-WTC_000256198
IAQ measurements collected for Stuyvesant High School in Feb–Mar 2002.
Similar indexed content
NYC-WTC_000256181
Report of IAQ measurements at Stuyvesant High School per BOE request.
Similar indexed content
NYC-WTC_000256216
IAQ measurements collected for Stuyvesant High School in Feb 2002.
Similar indexed content
NYC-WTC_000256233
IAQ measurements collected for Stuyvesant High School (Mar 2002).
Similar indexed content