IAQ field report, Stuyvesant High School, Feb 2002

Machine-extracted title · confidence 42%

ATC report of indoor air quality measurements conducted February 8, 2002 at Stuyvesant High School.

NYC-WTC_000255995–000255999
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 8, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 concentration range for these rooms was 14-18 pg/m^ with an average of approximately 17 ug/m\

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCConcentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; ■

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations of respirable particulates, COg, CO and TVOCs, were within applicable standards and guidelines. 2. All indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, Reviewed by: ATC ASSOCIATES INC.

Yiannis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003457796 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255998

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255998Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000256076

ATC memo for IAQ measurements at Stuyvesant High School on February 18, 2002.

Similar indexed content

NYC-WTC_000256028

ATC memo reporting IAQ measurements at Stuyvesant High School on Feb 12, 2002.

Similar indexed content

NYC-WTC_000256061

ATC memo detailing IAQ measurements at Stuyvesant High School dated February 14, 2002.

Similar indexed content

NYC-WTC_000255977

February 2002 IAQ measurements at Stuyvesant High School.

Similar indexed content

Compare copies and versions →