IAQ memo, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 42%

ATC memo with IAQ measurements at Stuyvesant High School.

NYC-WTC_000255821–000255824
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Field data sheets are found in Attachment 1. Readings began at 8;55 A.M. and concluded after 3:10 P.M. Pemperature

Indoor dry bulb temperature measurements ranged from 70.2 '’F to 76.4 °F. Twelve (12) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). Tliese measurements were collected from 4fh, 5^'*, 6th and 8th floors. The outdoor temperature range was 59.2 to 60.3 °F.

Relative Humidity

The relative humidity indoors ranged from 27.8 percent to 38.5 percent. Sixty-four (64) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.5 and 30.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 607 ppm to 2350 ppm. Three (3) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 550 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1250 ppm (background level ■+• 700 ppm). The highest reading/ 2350 ppm, was, in Room 737. Rooms with CO2 levels above the recommended maximum were found on 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1-2 ppm for all readings. Tliese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 ppm- T . ■ - .

Respirable Particulates (PM2^5)

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 34 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 26 and 57 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 4d\ 6^1 and 7^1 floors (See Attachment 1). The PM2.5 concentration range for those rooms. was 15-31 pg/m3 with an average of approximately 23 pg/m^, Tlie PM2.5 concentration range for the other rooms was 15-34 pg/m^ with an average of approximately 25 pg/nP. The average Pf^2.5 concentration for the entire school building was approximately 25 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2,5 concentration range for these rooms was 21-27 pg/m^ with an average of approximately 24 pg/m^.

CONFIDENTIAL, CITY_21MC100_003457582 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255823

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255823Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255518

IAQ measurements reported for Stuyvesant High School; December 10, 2001.

Similar indexed content

NYC-WTC_000274045

December 20, 2001 IAQ measurements at Stuyvesant High School for BOE.

Similar indexed content

Compare copies and versions →