Indoor air quality report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 42%

Report of IAQ measurements at Stuyvesant High School, Jan 25, 2002, for BOE.

NYC-WTC_000255705–000255709
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan January 28, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

Real-Time Enaiuonmental Measurements

ATC collected one hundred and fifteen (115) sets of real-time environmental measurements consisting of one hundred and thirteen (113) in the school building and two (2) outdoors. All ten floors of the school were surveyed. Tliese results are described below.

Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 1:36 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.1 °F to 72.8°F. None of the measurements were above the range of 68 to 75°F (at 50 percent, relative humidity) recommended by ASKRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature readings were 42.9 and 48.2°F.

Relative Humidity

The relative humidity indoors ranged from 23.2 percent to 29.8 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 29.8 and 30,0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 429 ppm to 831 ppm. None of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 410 and 442 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1142 ppm (background level -I- 700 ppm). Tlie highest reading, 831 ppm, was in Room 125. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM2,§)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 18 pg/nP. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 62 and 64 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''^, 4lh, 61*’ and 7ih floors (See Attachment 1). Tlte PM2 5 concentration range for those rooms

CONFIDENTIAL, CITY_21MC100_003457419 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255707

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255707Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000256164

Indoor air quality measurements conducted at Stuyvesant High School.

Similar indexed content

Compare copies and versions →