Mr. Bernard P. Orlan January 28, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Enaiuonmental Measurements
ATC collected one hundred and fifteen (115) sets of real-time environmental measurements consisting of one hundred and thirteen (113) in the school building and two (2) outdoors. All ten floors of the school were surveyed. Tliese results are described below.
Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 1:36 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 72.8°F. None of the measurements were above the range of 68 to 75°F (at 50 percent, relative humidity) recommended by ASKRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature readings were 42.9 and 48.2°F.
Relative Humidity
The relative humidity indoors ranged from 23.2 percent to 29.8 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 29.8 and 30,0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 429 ppm to 831 ppm. None of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 410 and 442 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1142 ppm (background level -I- 700 ppm). Tlie highest reading, 831 ppm, was in Room 125. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.
Respirable Particulates (PM2,§)
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 18 pg/nP. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 62 and 64 pg/m^.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''^, 4lh, 61*’ and 7ih floors (See Attachment 1). Tlte PM2 5 concentration range for those rooms
CONFIDENTIAL, CITY_21MC100_003457419 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000255707
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000256216
IAQ measurements collected for Stuyvesant High School in Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256233
IAQ measurements collected for Stuyvesant High School (Mar 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256164
Indoor air quality measurements conducted at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256181
Report of IAQ measurements at Stuyvesant High School per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256198
IAQ measurements collected for Stuyvesant High School in Feb–Mar 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256028
ATC memo reporting IAQ measurements at Stuyvesant High School on Feb 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256046
ATC memo for Stuyvesant High School IAQ measurements dated February 13, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255977
February 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255959
February 6, 2002 IAQ measurements for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256238
IAQ measurements collected for Stuyvesant High School (Mar 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256061
ATC memo detailing IAQ measurements at Stuyvesant High School dated February 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256013
ATC memo accompanying IAQ report for Stuyvesant High School, February 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000255755
ATC indoor air quality measurements at Stuyvesant High School; Jan 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255722
Indoor air quality measurements report for Stuyvesant High School, Jan 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401672
ATC memo documenting IAQ measurements taken January 25, 2002 at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311459
ATC IAQ report for Stuyvesant High School dated Feb 1, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255686
ATC indoor air quality report for Stuyvesant High School, January 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311384
ATC memo reporting IAQ measurements at Stuyvesant High School, Jan 25, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000256216
IAQ measurements collected for Stuyvesant High School in Feb 2002.
Similar indexed content
NYC-WTC_000256233
IAQ measurements collected for Stuyvesant High School (Mar 2002).
Similar indexed content
Indoor air quality measurements conducted at Stuyvesant High School.
Similar indexed content
NYC-WTC_000256181
Report of IAQ measurements at Stuyvesant High School per BOE request.
Similar indexed content
NYC-WTC_000256198
IAQ measurements collected for Stuyvesant High School in Feb–Mar 2002.
Similar indexed content