Mr. Bernard P. Orlan April 16, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.6°F to 75.3°F. Three (3) of the
measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 69.7°F to 70.9°F.
Relative Humidity
The relative humidity indoors ranged from 53.5 to 57.9 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 57.0 to 59.0 percent.
Carbon Dioxide ConcerUration
Carbon dioxide concentrations indoors ranged from 507 ppm to 809 ppm. All of the CO2
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 490 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1190 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 2 ppm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 ppm for all
collected readings.
Respirable Particulates (PM2_j) ppm.
Respirable particulate concentrations* indoors ranged between 16 pg/m3 to 28 pg/m3. None of
the measurements were above the NPAAQS of 65 pg/m or above the USEPA recommendation
of 40 pg/m^ for sensitive individuals and children. The average PM2.5 concentration for the
entire school building was approximately 21 pg/m^. The PM2 5 average concentration was
below the USEPA recommended concentration of 40 pg/m- for sensitive individuals and
children. The outdoor respirable particulate concentration measurements ranged from 19 to 28
pg/m3 with an average of 23 pg/m3.