NYC 9/11 Public Portal Document
Page 2 of 2
Process Description
WTC - Moretrench American
Bag Filter System
The bag filter system is design to remove suspended solids. There is no discharge limit for
suspend solids however, over time the solids will collect in the packing of the stripping tower
and reduce its efficiency. The bag filter to be provided is a Rosedale Multibag Filter. The
housing holds 6 separate bags. The maximum flow rate through the unit is 1,000 gpm, however,
we oversize this unit in terms of flow to extend the time between bag change outs. We intend to
use 10 micron filter bags. A bypass is provided so that flow can be diverted around the housing
during bag change out. From the bag filter the water moves to the top of the air stripping tower.
Air Stripping Tower
The air stripping tower is design to remove the MTBE from the water. The water is directed to
the top of the air stripping tower. The water cascades through packing media inside the tower
while air from a fan is blown into the base of the tower. The intermixing and redistribution of the
air/water stream takes place repeatedly as the as the air and water travel in opposite directions
through the packing. This contact between the two phases accomplishes the mass transfer of
MTBE in water to air.
The clean water drops into a sump and will flow by gravity to the discharge point estimated to be
50 feet away without significant elevation change. A flow meter will be provided to record
discharge quantities to the sewer.
The air, which now is contaminated with MTBE will be collected at the top of the tower and
removed from the air stream using a vapor phase carbon box adsorber.
Vapor Phase Box Adsorber and Carbon
The carbon usage rate as calculated by US Filter Corporation is 101 pounds per day at 90%
relative humidity. The box adsorber to be provided holds 20,000 pounds of carbon. Given the
usage rate the carbon will have to be changed every 190 days. Sample ports will be installed
within the carbon bed to aid in determining carbon break through. When a change out is required
it is our intent to exchange the box adsorbers with a new one as opposed to removing spent
carbon and replacing with new onsite, however we will need access to the adsorber by a lift
truck. The spent carbon will be reactivated at US Filters Arizona Facility.
Control System
The control system will consist of on/off pump floats for the control of the water level in the
equalization tank. A high level float will also be installed to shut down the sump pumps in the
event of a high water level in the equalization tank.
A high level float will also be installed in the sump of the air stripping tower to turn of the feed
pumps in the event of a high level in the sump which would be caused by a clogged discharge
pipe
GROUND/WATER TREATMENT & TECHNOLOGY, INC.
CONFIDENTIAL INSURANCE INFORMATION, CITY_2IMCl00_006225138
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000251939
OCR can misread numbers and units. Confirm readings against the page image before using them.