Mr. Bernard P. Orlan May 30, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M_____________________________ ATC Project No. 15-19125-0289 Real-Time Environmemal Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 1:10 P.M. and concluded at approximately 2:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 73.3 °F to 77.8 °F. All of the indoor measurements were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature measurements was 76.1 °F for all readings.
Relative Humidity
The relative humidity indoors ranged from 46.1 to 54.8 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements was 59.1 percent for all readings.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 598 ppm to 1425 ppm. Four (4) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 541 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1241 ppm (background level + 700 ppm). The highest reading was recorded in room 401 at 2:00 PM with 26 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations was 1 ppm for all collected readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for all collected readings.
Respirable Particulates (PM2,5) ppm.
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 26 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 16 pg/m^. The outdoor respirable particulate concentration measurements ranged from 46 to 54 pg/m^ with an average of 51 pg/m^.
CONFIDENTIAL, CITY_21MC1OO_OO5759848 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249941
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000250008
Indoor air quality measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249931
ATC IAQ measurements at PS 150M, May 31, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249972
ATC report of IAQ measurements at a NYC school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249956
ATC IAQ measurements at P.S. 150M, prior to occupancy, BOE referenced.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250012
ATC IAQ measurements collected at school site in mid-June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250000
Indoor air quality measurements at PS 150M before occupancy recommencement.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249976
Indoor air quality measurements taken at school site during June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178775
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 29, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000374932
ATC IAQ measurements at school prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250012
ATC IAQ measurements collected at school site in mid-June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394501
Indoor air quality measurements collected April 29, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253831
Indoor air quality measurements at PS 150 for occupancy pre-reporting.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000250008
Indoor air quality measurements at school prior to re-occupancy.
Similar indexed content
NYC-WTC_000249931
ATC IAQ measurements at PS 150M, May 31, 2002, prior to re-occupancy.
Similar indexed content
NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
Similar indexed content
NYC-WTC_000249972
ATC report of IAQ measurements at a NYC school prior to re-occupancy.
Similar indexed content
NYC-WTC_000249956
ATC IAQ measurements at P.S. 150M, prior to occupancy, BOE referenced.
Similar indexed content