NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗ATC IAQ measurements at PS 150M, May 31, 2002, prior to re-occupancy.
NYC-WTC_000249931–000249934OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 31,2002 Indoor Air Quality Assessment Page 3 P. S, 150M________________________________ ATC Project No. 15-19125-0289 Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 1:10 P.M. and concluded at approximately 2:40 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.8 °F to 79.1 °F. One (1) of the indoor measurements was above and one (1) measurement was below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature measurements ranged from 82.7 °F to 82.9 °F.
Relative Humidity
The relative humidity indoors ranged from 36.6 to 55 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 46.1 to 46.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 551 ppm to 1113 ppm. All of the CO2 indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 551 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1251 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. TTie school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations was 1 ppm for all collected readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for all collected readings.
Respirable Particulates (PM2 ^) ppm.
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 17 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 13 pg/m^. The outdoor respirable particulate concentration measurements ranged from 21 to 22 pg/m^ with an average of 21 pg/nC.
CONFIDENTIAL, CITY_21MC100_005759839 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249933
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250008
Indoor air quality measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249976
Indoor air quality measurements taken at school site during June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249956
ATC IAQ measurements at P.S. 150M, prior to occupancy, BOE referenced.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249912
ATC IAQ measurements at PS 150M, May 23–24, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250000
Indoor air quality measurements at PS 150M before occupancy recommencement.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250020
Sequence of IAQ measurements at PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249876
ATC reports IAQ measurements at PS 150M, May 15, 2002, to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249768
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000250012
ATC IAQ measurements collected at school site in mid-June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178006
Letter reporting indoor air quality measurements collected at P.S. 150M on June 19, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253762
ATC IAQ report for PS 150M prior to occupancy, per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374920
ATC IAQ measurements at school prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374860
ATC measures indoor air quality at PS 150M before re-occupancy for DOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249956
ATC IAQ measurements at P.S. 150M, prior to occupancy, BOE referenced.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
Similar indexed content
NYC-WTC_000250008
Indoor air quality measurements at school prior to re-occupancy.
Similar indexed content
NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
Similar indexed content
NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
Similar indexed content
NYC-WTC_000249976
Indoor air quality measurements taken at school site during June 2002.
Similar indexed content