NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, PS 150M, May 2002

Machine-extracted title · confidence 42%

ATC reports IAQ measurements at PS 150M, May 14, 2002, to evaluate air quality before re-occupancy.

NYC-WTC_000249872–000249875
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 15,2002 Indoor Air Quality Assessment Page 4 P.S. 150M ATC Project No. 15-19125-0289 I respirable particulate concentration measurements ranged from 20 to 25 pg/m^ with an average of 22 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • There was construction work going on in the plaza; • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulate ,CO and TVOCs were within applicable standards and guidelines; 2. All temperature measurements were below the range of 73 to 79° F (at 50 percent relative humidity recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. All measurements of relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. All CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212.

Sincerely, Reviewed by: .4 rC ASSOCIA TES l^C.

/ yA^iannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CONFIDENTIAL, CITY_21MC100_005759751 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000249875

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000249875Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →