Indoor air quality measurements for PS 150M, prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements for PS 150M prior to re-occupancy.
NYC-WTC_000249840–000249843OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 9, 2002 Indoor Air Quality Assessment Page 3 P.SaSOM ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 1:10 P.M. and concluded at approximately 2:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 73.3°F to 77.8^. All of the measurements were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (summertime conditions). The outdoor temperature measurements ranged from 74.1°F to 74.3°F.
Relative Humidity
The relative humidity indoors ranged from 32.5 to 42.5 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 27.2 to 27.4 percent.
CqrbpnJDipxideCpncentrqtipn
Carbon dioxide concentrations indoors ranged from 471 ppm to 1450 ppm. One (1) of the CO2 measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 416 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1116 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were 0 ppm for all collected readings.
Respirable Particulates (PM2,s) ppm.
Respirable particulate concentrations* indoors ranged between 17 pg/m^ to 34 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 24 pg/m^. The outdoor respirable particulate concentration measurements ranged from 20 to 27 pg/m^ with an average of 24 pg/m^.
CONFIDENTIAL, CITY_21MC1OO_OO5759714 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249842
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249796
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250008
Indoor air quality measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374740
ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250012
ATC IAQ measurements collected at school site in mid-June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249828
Indoor air quality measurements collected on May 6-9, 2002 for PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249804
Report of IAQ measurements at PS 150M to assess air quality prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249912
ATC IAQ measurements at PS 150M, May 23–24, 2002, prior to re-occupancy.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249876
ATC reports IAQ measurements at PS 150M, May 15, 2002, to evaluate air quality before re-occupancy.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249896
ATC IAQ measurements at PS 150M prior to occupancy, May 21, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
Similar indexed content
NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
Similar indexed content
NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
Similar indexed content
NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
Similar indexed content
NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
Similar indexed content