Mr. Bernard P. Orlan May 7, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Project No. 15-19125-0289
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATIONCRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditionsfor Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79"F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AMA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_0 05759695 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249829
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249876
ATC reports IAQ measurements at PS 150M, May 15, 2002, to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177966
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249796
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249804
Report of IAQ measurements at PS 150M to assess air quality prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374740
ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374724
ATC IAQ measurements at PS 150M for school building re-occupancy assessment, May 1, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249784
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000410495
ATC measurements of IAQ at PS 150M prior to re-occupancy for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410443
IAQ report for PS 150M following measurements on Feb 12, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300633
ATC IAQ report covering measurements at PS 150M for re-occupancy
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289410
IAQ measurements collected for P.S. 150M; March 22, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375465
Indoor air quality measurements for P.S. 150M requested by BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
Similar indexed content
NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
Similar indexed content
NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
Similar indexed content
NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
Similar indexed content
NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
Similar indexed content