NYC-WTC_000410503
ATC measurements of IAQ at PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗ATC report detailing IAQ parameters for PS 150M, mid-April 2002.
NYC-WTC_000249748–000249751OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 16, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289
REAL-TIME Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.6°F to 75.3°F. Three (3) of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 69.7°F to 70.9°F.
Relative Humidity
The relative humidity indoors ranged from 53.5 to 57.9 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 57.0 to 59.0 percent.
CarbonDioxideConcentration
Carbon dioxide concentrations indoors ranged from 507 ppm to 809 ppm. All of the CO2 measurements were within the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 490 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1190 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 ppm for all collected readings.
Respirable Particulates (PM2,5) ppm.
Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 28 pg/m3. None of the measurements were above the NPAAQS of 65 pg/m or above the USEPA recommendation of 40 pg/m3 for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 21 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 19 to 28 pg/m3 with an average of 23 pg/m^.
CONFIDENTIAL, CITY_21MC100_005759562 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249750
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000410503
ATC measurements of IAQ at PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249732
ATC indoor air quality measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410527
IAQ measurements collected for BOE pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249700
IAQ measurements at PS 150M before re-occupancy; scope described.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410451
IAQ measurements at PS 150M; BOE pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249740
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410567
IAQ measurements report for PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410507
ATC IAQ measurements for BOE pre-occupancy at PS 150M.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249724
ATC IAQ measurements report for PS 150M in April 2002 before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410559
Report of IAQ measurements at a NYC school building prior to re-occupancy, March 7, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410551
IAQ data collection prior to re-occupancy at PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214968
Letter from ATC Associates reporting indoor air quality measurements collected at PS 150M on March 27, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000249740
ATC IAQ measurements report for PS 150M, April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410503
ATC measurements of IAQ at PS 150M prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300811
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410467
IAQ measurements collected Feb 15, 2002 at PS 150M for BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249724
ATC IAQ measurements report for PS 150M in April 2002 before re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178726
Letter from ATC Associates providing indoor air quality measurement results collected at P.S. 150M prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000410503
ATC measurements of IAQ at PS 150M prior to re-occupancy.
Similar indexed content
NYC-WTC_000249732
ATC indoor air quality measurements report for PS 150M, April 2002.
Similar indexed content
NYC-WTC_000410527
IAQ measurements collected for BOE pre-occupancy evaluation.
Similar indexed content
NYC-WTC_000249700
IAQ measurements at PS 150M before re-occupancy; scope described.
Similar indexed content
NYC-WTC_000410451
IAQ measurements at PS 150M; BOE pre-occupancy evaluation.
Similar indexed content