Wipe samples for PCBs, PS 234M, Dec 2001

Machine-extracted title · confidence 50%

Memorandum reporting wipe samples for PCBs and related hydrocarbons at PS 234M.

NYC-WTC_000249604–000249605
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan December 17, 2001 Wipe Sampling for PCBs and PAHs Page 2 P. S. 234 ("Manhattan) ATC Project No. 15-19125-0279

WIPE SAMPLING RESULTS

ATC submitted ten samples for PCBs and ten samples for PAHs (plus one blank) to PSC for analysis. Copies of the laboratory reports are provided in Attachments 1 and 2. Samples were taken from areas specified by the parents association consultant. The sample area for each sample was 100 square centimeters (lOOcm^) with the exception of a windowsill sample that was 64 cm2. The areas sampled were:

• Cafeteria - windowsill; • Kitchen - serving windowsill; • Room 116 - table surface; • Room 120 - windowsill; • Room 211 - table surface; • Library - table surface; • Library - bookcase surface; • Room 305 - bookcase surface; • Room 316 - table surface; • Gymnasium - landing.

Each sample was analyzed for seven (7) PCB compounds (Attachment 1) and sixteen (16) PAHs (Attachment 2). The PCB results of all samples were below the reporting limits (2.0 micrograms/sample). The PAH results were also below the reporting limits (5.0 micrograms/sample), the same level was found in the blank.

Currently, the Environmental Protection Agency spill clean-up standard for PCBs on non-porous surfaces is 10 micrograms per 100 square centimeters or less (<10ug/100cm2) as stated in 40 CFR 761. No regulatory standards have been established for PAHs on surfaces.

It is our pleasure to provide these indoor environmental services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 212 or 261.

Sincerely, A TC ASSOCIA TES INC.

James R. Cohn, CIH, CSP Regional Manager Industrial Hygiene Division

Attachments

CONFIDENTIAL, CITY_2IMCl00_003444928 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000249605

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000249605Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Memo/Letter, wipe sample report

NYC-WTC_000385697

ATC Associates report memo detailing wipe samples for hydrocarbons at World Trade Center site.

Similar indexed content

Compare copies and versions →