Sampling Methodology
Sampling and analysis for Dioxins on surfaces was conducted utilizing sterile wipes impregnated
with hexane. A known surface area (100cm x 100cm) was wiped and the wipe sample submitted
to the lab and analyzed.
4.5 Results of Air Sampling and Analysis
Air sampling was conducted for a comprehensive list of substances as indicated above. All air
samples collected by TRC were collected with the HVAC operating. The following discussion
summarizes the findings of the air sampling program.
4.5.1 Asbestos Air Sampling and Results
Air Sampling Results
Sixty (60) air samples (excluding blanks) were collected in an aggressive manner and analyzed
by TEM for asbestos. Results of asbestos air samples are presented in Table 10 of Appendix A.
None of the samples were found to be greater than 70 structures per square millimeter (s/mm^),
which is the AHERA clearance criterion established for re-occupancy following asbestos
abatement in schools. In fact, all samples were less than the detection limit of the analytical
method, that is no asbestos fibers were found in any of the air samples.
Aggressive Asbestos Air Sampling Methodology
Asbestos air samples were collected using “aggressive” techniques to simulate a worst-case
scenario and re-suspend into the air any settled dust that could be the source of asbestos fibers.
Aggressive sampling techniques involve agitating air within the space using an electric leaf
blower. The exhaust from the leaf blower is directed against vertical and horizontal surfaces on
which dust may have settled. Particular attention is given to hard to clean areas such as comers
of the room and behind desks. Additionally, the exhaust was directed into the air to assist air
movement and circulation. During the clearance air sampling period, the building’s HVAC
system in the areas was in operation.
Asbestos Standard
20