NYC 9/11 Public Portal Document
Ten (10) of the initial round of fifty-eight (58) samples from the HVAC system contained a level
of asbestos that exceeded the individual sample target post-cleaning concentration of 10,000
str/cm^. The ten samples were located as follows:
• Southeast supply duct on the 6*^ floor,
• Southwest return duct on the 2“*’ floor,
• Southwest ceiling tile on the 20* floor,
• Air handler supply # 11 on the 2 floor,
• Return air duct #F 12 on the 21®‘floor,
• Air handler supply#! on the 2 floor,
• Air handler supply #2 on the 7* floor,
• Air handler supply #3 on the 7* floor,
• Air handler supply #4 on the 7* floor, and
• Supplemental supply air handler in the LAN room on the 20* floor.
In response to this and the lead results described in Section 4.4.3, ZAR hired a National Air Duct
Cleaning Association (NADCA) certified duct cleaning contractor to re-clean and encapsulate
the interior supply ducts, supply risers, return ducts and risers, and re-clean the HVAC fan units
serving the NYCLD spaces. The building has reported that once the cleaning is complete for the
NYCLD space, the remaining interior HVAC units and ductwork supplying air for the remainder
of the building will be re-cleaned as well.
The HVAC re-cleaning effort was performed by Branch Services (Branch), Cunningham
Mechanical (Cuimingham), and Indoor Air Professionals (lAP). Branch is a New York State
certified asbestos abatement contractor and Cunningham and LAP are NADCA certified duct
cleaning contractors. Branch conducted power-washing of fan units and Cunningham and LAP
performed duct cleaning activities. Branch applied an encapsulant to the HVAC system surfaces
subsequent to HVAC cleaning. Encapsulating is the process of applying of a thin layer of
sprayed liquid material that creates a membrane locking down any residual dust subsequent to
cleaning operations. Cleaning activities utilized HEPA filtered equipment and followed
NADCA protocols.
15
CITY_21 MC100_014587097
NYC-WTC_000243720
OCR can misread numbers and units. Confirm readings against the page image before using them.