• Surface Dust. Between January 11 and March 29, 2002, TRC collected two hundred and
forty five (245) dust/surface samples, with samples taken fi-om each floor in a number of
locations in the NYCLD space and the HVAC system. These dust/surface samples were
tested for asbestos, lead, PCBs, and dioxins. Post re-cleaning dust testing for asbestos in the
NYCLD office space is continuing, as explained below in 4.4.1.
Subsequent to ZAR’s initial cleaning activities in the fall of 2001, TRC’s sampling results
identified elevated concentrations of asbestos in the carpeting, in one sample taken on the top
of a perimeter induction unit, in the computer and printer equipment, and in the HVAC
system. Elevated concentrations of lead were also found on some surfaces within the
NYCLD space and the HVAC system. As a result of these findings, the NYCLD has
replaced the carpeting, computer, fax, printer and copier equipment and painted the perimeter
induction units. In addition, extensive re-cleaning of the space occupied by the NYCLD and
the HVAC system has been performed. The results of asbestos and lead sampling conducted
to date by TRC after the re-cleaning were below target individual sample and geometric
mean concentrations. No PCBs were detected in any of the wipe samples. Low levels of
dioxin were detected in wipe samples of surfaces within NYCLD space. TRC has conducted
a site specific human health risk assessment using the sampling data. The assessment
indicated that the concentrations of dioxin do not represent a significant increased risk of
cancer (i.e., less than one in one million) to building occupants. The entire NYCLD space is
being re-cleaned.
3.0 DESCRIPTION OF TASKS PERFORMED BY TRC
This section of the report reviews the tasks performed by TRC and identifies the methodologies
used in connection with the environmental assessment of the conditions at 100 Church Street.
3.1 Review of Building Systems
Beginning in January 2002, TRC met with ZAR and its consultant, the Ambient Group, Inc,, to
review and inspect the heating, ventilation and air conditioning (HVAC) system that serves the
NYCLD spaces. The purpose of the review was to identify how the HVAC system is configured
to ultimately determine how the air is filtered, conditioned and transported to the space occupied
5
CITY_21 MCI 00_014586878
NYC-WTC_000243572