NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan January 18, 2002
Indoor Air Quality Assessment Page 4
P. S. 89 (Manhattan)__________ _________ _ _____________ ATC Project No. 15-19125-0297
concentration for the entire school building was approximately 29 pg/m^.The outdoor respirable
particulate concentration ranged from 41 -46 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was not occupied at the time of the assessment;
• No smoke odor was detected in the building;
• One window on floor hallway by staircase #2 was open
FINDP^GS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, COo, CO and TVOCs were within applicable
standards and guidelines,
2. One (1) indoor measurement of relative humidity were within the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort. All other measurements were below the
ASHRAE-recommended range;
3. Three (3) temperature measurements were above and four (4) were belpw the range of 68 to
750 E (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during ‘
the heating season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions aboi.it. this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
A TC ASSOCIATES INC.
Reviewed by:
Andreas C. Andreou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014659985
NYC-WTC_000236980
OCR can misread numbers and units. Confirm readings against the page image before using them.