AMBIENT AIR AND DUST SAMPLING PROTOCOL for PS/IS89M. Page 5 of 8
In the event that any of PLM analysis detect more than 1 % by weight of fiberglass, BOE will
immediately notify the UFT, the school principal, the school custodian and the PA consultant.
The said parties will assess the situation and implement the appropriate response action(s).
LEAD SURFACE DUST
• First floor hallway outside cafeteria - 2 samples.
• Cafeteria - one sample.
• Gymnasium - one sample.
• Auditorium - one sample.
• Classroom with north side unit ventilators - one sample immediately after the last class.
• Classroom with east side unit ventilators - one sample immediately after the last class.
• Classroom with south side unit ventilators - one sample immediately after the last class.
• Second floor Hallways south end - one samples immediately after the last class.
• Fourth floor Hallways south end - one samples immediately after the last class.
All dust wipe samples taken shall be analyzed in accordance with EPA7082 method via
Flame Atomic Absorption (FAA).
Dust wipe results shall be considered satisfactory when the levels obtained are below the
EPA new levels for clearing a work area for re-occupancy after an EPA defined lead
abatement is performed, as specified in 40 CFR §745.227(e)(8)(viii).
Floors; 40 micrograms of lead per square foot
Window Sills; 250 micrograms of lead per square foot
Dust wipe results shall be considered unsatisfactory when the levels obtained are greater
than the EPA new levels for clearing a work area for re-occupancy after an EPA defined lead
abatement is performed, as specified in 40 CFR §745.227(e)(8)(viii).
Floors; 40 micrograms of lead per square foot
Window Sills; 250 micrograms of lead per square foot
Results from samples collected shall be reported to BOE, UFT, School Principal and the PA
consultant within 24 hours.
In the event that unsatisfactory results are obtained, the following actions are to be
implemented;
1. Perform general dust clean up of all areas/classrooms with unsatisfactory results.
2. Lead specific cleaner shall be utilized.