Mr. Bernard P. Orlan May 8, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Envikoxmemal .Measikemenis
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 71.1 °F to 85.9 °F. Thirty-six (36) of the indoor measurements collected were below and two (2) indoor measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 71.2 °F to 80.1 °F.
Relative Humidity
The relative humidity indoors ranged from 45.3 percent to 55.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 48.0 to 55.4 percent.
Ccu-bon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 426 ppm to 1261 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 493 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1193 ppm (background level + 700 ppm). The highest reading (1261 ppm) was measured in room # 507 around 8:30 A.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings..
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 25 pg/m^ with an average of 20 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the outdoor instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
CITY_21MC100_002891369
NYC-WTC_000223582
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180085
Report of indoor air quality measurements collected at the referenced school on June 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179968
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 1, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180081
Report of indoor air quality measurements collected at the referenced school on May 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000180085
Report of indoor air quality measurements collected at the referenced school on June 7, 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Buildings in this record
Machine-extracted building matches; verify each source. Buildings, never households.
- 100 Trinity Place · 1 pages · confidence 0.15 · verify page 1
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similar indexed content
Similar indexed content
NYC-WTC_000180085
Report of indoor air quality measurements collected at the referenced school on June 7, 2002.
Similar indexed content