Indoor Air Quality Assessment Page 4
P. S.TSOM ATC Project No. 15-19125-0289
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
Type Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
SKunSGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of indoor respirable particulates, CO2, CO, and TVOCs were within
applicable standards and guidelines.
2. Five (5) of the indoor measurements were above and none of the measurements were below
the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE
Standard 55-1992 during the mechanical cooling season (summertime conditions).
3. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent
for occupant comfort.