Mr. Bernard P. Orlan June 4, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M_______________________________ ATC Project No. 15-1912.5-0297 Real-Time Environmental Measuremei^

ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:40 A.M. and concluded at approximately 10:50 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.3 °F to 74.6 °F. Thirty- eight (38) of the indoor measurements for temperature were below and none of the measurements were above the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 70.1 °F to 70.2 °F ..

Relative Humidity

The relative humidity indoors ranged from 26.1 to 32.3 percent. Thirty-four (34) of the indoor measurements for relative humidity were bellow and none of the readings were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements was 28.8 percent for all readings.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 510 ppm to 1301 ppm. None of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 660 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1360 ppm (background level + 700 ppm). Based on the field data collected the highest reading was recorded in room 528 at 10:10 AM with 29 occupants. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all collected readings.

Respirable Particulates (PM2.51

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 12 pg/m^. The average PM2.5 concentration for the entire school building was approximately 10 pg^mY All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor

CITY_21MC100_0 02863291

NYC-WTC_000211006

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000211006Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →