10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000202383
Label derived from the City's folder field. The City does not supply document titles.NYC-WTC_000202383–000202386
OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan September 10, 2002 Indoor Air Quality Assessment Page 3 P.S. 42 M ATC ProiectNo. 15-19125-0342
Real-time environmental Measurements
ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-eight (48) in the school building and two (2) outdoors. All floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected during school hours. The results are described below.
Temperature
Indoor diy bulb temperature measurements ranged from 72.0 to 76.4 °F. Six (6) of the indoor temperature measurements were below the range of 73 to 79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements were 75.7 and 82.7 °F.
Relative Humidity
The relative humidity indoors ranged from 47.9 percent to 76.1 percent. Twelve (12) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 58.4 and 58.7 percent. The high ambient relative humidity likely contributed to the elevated particulate levels reported below.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 636 ppm to 1396 ppm. One (1) of indoor measurement for CO2 was above the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level. The average outdoor (background) COg concentration was 681 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1381 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COp indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm and 3ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 33 pg/m^ to 96 pg/m^. Forty- five (45) of the indoor measurements collected for PMpy were above the USEPA recommended concentration of 40 pg/m- for sensitive individuals such as asthmatic people and children. The two outdoor respirable particulate concentrations were 182 pg/m^ and 65 pg/m^ with an average of 124 pg/m3. The Dust Trak® detects volatile aerosol particles and may be affected by elevated humidity and airborne moisture droplets in addition to dust particles.
CITY_21MC100_003272426
NYC-WTC_000202385
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182883
Report of indoor air quality measurements collected at PS 234M on February 13, 2002, to assess acceptable air quality conditions.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content