Mr. Bernard P. Or Ian October 19. 2001 Indoor Air Quality .Assessment Page 2 Stuvvesant Hish School fM477) ATC Project No. 15-19125-0246

The assessment was performed consistent w'ith generally accepted indoor air quality assessment practices. .As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in air contaminant concentrations, and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the Board of Education as a guide to assess the need for further improvements in current indoor air quality control activities.

E^^ALUATION CRITERIA

Currently, there are no regulators' standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

I'eniiicition for Acceptable !iick>or Air Quality (ASHRAE 62-J999J, American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE co-J992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

PARAJMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ASHRAE 62)_________________ Respirable Particles 50 micrograms per cubic meter USEPA NPAAQS (as cited in (PM 10) of air (pg/m^) ASHRAE 62) Temperature Summer: 73-78.5°F at 50% RH ASHRAE 55 Winter: 69-76°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile ] ppm Organic Compounds AIHA (TVOC)_______________________________________ USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

CITY_21MC100_003045606

NYC-WTC_000197519

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000197519Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →