NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 17, 2002
Indoo ' Air Quality Assessment Page 4
H.S, cf Economics and Finance tM833) ATC Project No. 15-19125-0291
TVOC Concentration
TVOt/s were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
obsi:rvations
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• b o smoke odor was detected in the building;
FINIUNGS
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO,, CO, and TVOCs were below applicable standards and
guidelines.
2. .Ml of the indoor measurements for temperature were within the range of 73 °F to 79°F (at
50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the
summer season.
3. /ill of the indoor measurements for relative humidity were within ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
4. Tione of the indoor measurements for respirable particulates were above the NPAAQS of 65
pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less i:n
serodynamic diameter and the USEPA recommended concentration of 40 pg/m’ for sensitive
individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext 211 or
212.
Sincerely, Reviewed by:
/(TC ASSOC lA TES INC.
Amei J^l James R. Cohn, CIH, CSP
Senior ^oject Manager Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_003462886
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000180092
OCR can misread numbers and units. Confirm readings against the page image before using them.