Mr. Bernard P. Orlan April 24, 2002
Indoor Air Quality Assessment Pages
P. S. 150M______________________________ ATC Project No. 15-19125-0289
REzKL-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.4 °F to 75.8 °F. Twelve (12) indoor
measurements for temperature were below and eighteen (18) measurements were within the
range of 73 to 79 °F (at 50 percent relative humidity) as recommended by the ASHRAE Standard
55-1992 during the summer conditions. The outdoor temperature measurements ranged from
45.8 °F to 47.6 °F.
Relative Humidity
The relative humidity indoors ranged from 23.7 to 44.2 percent. Thirteen (13) of the indoor
measurements were below and seventeen (17) measurements were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity
measurements ranged from 36.3 to 38.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 610 ppm to 980 ppm. All of the COg
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
COg concentration was 435 ppm. Therefore, the maximum acceptable level of COg at this
location was 1135 ppm (background level -1- 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of COg indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations was 0 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from
0 ppm to 1 ppm.
Respirable Particulates (PM2,§) ppm.
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 14 pg/m^. All of the
indoor and outdoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ for 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and
the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The average
PM2.5 concentration for the entire school building was approximately 10 pg/m^. The outdoor