Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on April 23, 2002.

NYC-WTC_000178746–000178749
Page image
Scanned page image, NYC-WTC_000178748
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 24, 2002 Indoor Air Quality Assessment Pages P. S. 150M______________________________ ATC Project No. 15-19125-0289 REzKL-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at approximately 1:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 67.4 °F to 75.8 °F. Twelve (12) indoor measurements for temperature were below and eighteen (18) measurements were within the range of 73 to 79 °F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer conditions. The outdoor temperature measurements ranged from 45.8 °F to 47.6 °F.

Relative Humidity

The relative humidity indoors ranged from 23.7 to 44.2 percent. Thirteen (13) of the indoor measurements were below and seventeen (17) measurements were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 36.3 to 38.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 610 ppm to 980 ppm. All of the COg measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) COg concentration was 435 ppm. Therefore, the maximum acceptable level of COg at this location was 1135 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of COg indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide indoor concentrations was 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 0 ppm to 1 ppm.

Respirable Particulates (PM2,§) ppm.

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 14 pg/m^. All of the indoor and outdoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ for 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. The outdoor

CITY_21MC100_002893943

NYC-WTC_000178748

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000178748Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000177954

Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.

Similar indexed content

NYC-WTC_000177946

Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.

Similar indexed content

Compare copies and versions →